Theory or Operation of Inductive Proximity Sensors How Inductive Proximity Sensor Works





Theory or Operation of Inductive Proximity Sensors | How Inductive Proximity Sensor Works?

 In this section we will look at Inductive proximity sensors, and how they detect the presence of an object without coming into physical contact with it. Inductive proximity sensors are available in a variety of sizes and configurations to meet varying applications. Specific sensors will be covered in more detailed in the following section.






Electromagnetic Coil and Metal Target


The sensor incorporates an electromagnetic coil which is used to detect the presence of a conductive metal object. The sensor will ignore the presence of an object if it is not metal.
 




Inductive proximity sensors are operated using an Eddy Current Killed Oscillator (ECKO) principle. This type of sensor consists of four elements: coil, oscillator, trigger circuit, and an output. The oscillator is an inductive capacitive tuned circuit that creates a radio frequency. The electromagnetic field produced by the oscillator is emitted from the coil away from the face of the sensor. The circuit has just enough feedback from the field to keep the oscillator going.

When a metal target enters the field, eddy currents circulate within the target. This causes a load on the sensor, decreasing the amplitude of the electromagnetic field. As the target approaches the sensor the eddy currents increase, increasing the load on the oscillator and further decreasing the amplitude of the field. The trigger circuit monitors the oscillator’s amplitude and at a predetermined level switches the output state of the sensor from its normal condition (on or off). As the target moves away from the sensor, the oscillator’s amplitude increases. At a predetermined level the trigger switches the output state of the sensor back to its normal condition (on or off).
 





Operating Voltages 

 Inductive proximity sensors include AC, DC, and AC/DC (universal voltage) models. The basic operating voltage ranges are from 10 to 30 VDC, 15 to 34 VDC, 10 to 65 VDC, 20 to 320 VDC, and 20 to 265 VAC.

Output Configurations 

 Three-wire, DC proximity sensor can either be PNP (sourcing) or NPN (sinking). This refers to the type of transistor used in the output switching of the transistor. The following drawing illustrates the output stage of a PNP sensor. The load is connected between the output (A) and the negative side of the power supply (L-). A PNP transistor switches the load to the positive side of the power supply (L+). When the transistor switches on, a complete path of current flow exists from L- through the load to L+. This is also referred to as current sourcing since in this configuration conventional current is (+ to -) sourced to the load. This terminology is often confusing to new users of sensors since electron current flow (-to +) is from the load into the sensor when the PNP transistor turns on.





The following drawing illustrates the output of an NPN sensor. The load is connected between the output (A) and the positive side of the power supply (L+). An NPN transistor switches the load to the negative side of the power supply (L-). This is also referred to as current sinking since the direction of conventional current is into the sensor when the transistor turns on. Again, the flow of electron current is in the opposite direction.





Comments

Popular posts from this blog

PID instruction in Allen Bradley PLC Closed Loop Control

PID instruction in Allen Bradley PLC [Proportional/Integral/Derivative] Closed Loop Control For   Processor SLC 5/02SLC 5/03SLC 5/04SLC 5/05    MicroLogix 1200 and MicroLogix 1500 (A special PID file replaces the old integer file control block.) Description of PID in PLC   This output instruction is used to control physical properties such as temperature, pressure, liquid level, or flow rate of process loops. The PID instruction normally controls a closed loop using inputs from an analog input module and providing an output to an analog output module as a response to effectively hold a process variable at a desired set point. The PID equation controls the process by sending an output signal to the actuator. The greater the error between the setpoint and the process variable input, the greater the output signal, and vice versa. An additional value (feed forward or bias) can be added to the control output as an offset. The result of the PID calculation (control vari...

NE566 Function Generator Circuit Diagram

The NE566 Function Generator is a Voltage-Controlled Oscillator of exceptional linearity with buf fered square wave and triangle wave outputs. The frequency of oscillation is determined by an external resistor and capacitor and the voltage applied to the control terminal. The Oscillator CAN be programmed over a ten-to-one frequency range by proper selection of an external resistance and modulated over a ten-to-one range by the control voltage, with exceptional linearity.  FMAX = 1 MHz     WIDE 1000:1 Continuous Sweep Possible  NE566 Function Generator Circuit Diagram Pdf Datasheet  Sourced by : Circuitsstream

Long Loopstick Antenna Circuit Diagram

Circuit Diagram  Description Wound on a 3 foot length of PVC pipe, the long loopstick antenna was an experiment to try to improve AM radio reception without using a long wire or ground. It works fairly well and greatly improved reception of a weak station 130 miles away. A longer rod antenna will probably work better if space allows. The number of turns of wire needed for the loopstick can be worked out from the single layer, air core inductance formula: Inductance = (radius^2 * turns^2) / ((9*radius)+(10*length)) where dimensions are in inches and inductance is in microhenrys. The inductance should be about 230 microhenrys to operate with a standard AM radio tuning capacitor (33-330 pF). The 3 foot PVC pipe is wound with approximately 500 evenly spaced turns of #24 copper wire which forms an inductor of about 170 microhenrys, but I ended up with a little more (213uH) because the winding spacing wasn't exactly even. A secondary coil of about 50 turns is wound along the length of th...