A very simple Ionization Smoke Detector with Interconnect and Timer alarm circuit can be constructed using the A5367 low-current, CMOS circuit that provides all of the required features for an ionization-type smoke detector. A very nice thing at this ionization smoke detector circuit CMOS ic manufactured by Allegro MicroSystems is the interconnection features , which allows as many as 125 units to be interconnected so that if any unit senses smoke all units will sound their alarm. In addition, special features are incorporated to facilitate alignment and test of the finished smoke detector.

This detector needs to be powered by a 9 volts DC power supply (or a 9 volts battery ) .Circuit require few external components and is very easy to be configured . As you can see in this diagram , the sound alarm is “produced “ by an piezoelectric element .

Ionization Smoke Detector Circuit Diagram


Use an external resistor in point A to adjust sensitivity for a particular smoke chamber. Select resistor from point B is to reduce sensitivity during Timer mode.A resistor to VSS or VDD may be added to point C pin to modify low battery voltage threshold. Value of components marked with D will vary, based on the piezoelectric horn used.

An internal timer is provided that can be used in various configurations to allow a period of reduced smoke detector sensitivity, referred to as Timer (or Hush) mode. Internal test circuitry allows low battery check by holding the FEEDBACK and OSC CAP pins low during power-up, then reducing VDD and monitoring the HORN1 pin

Comments

Popular posts from this blog

PID instruction in Allen Bradley PLC Closed Loop Control

PID instruction in Allen Bradley PLC [Proportional/Integral/Derivative] Closed Loop Control For   Processor SLC 5/02SLC 5/03SLC 5/04SLC 5/05    MicroLogix 1200 and MicroLogix 1500 (A special PID file replaces the old integer file control block.) Description of PID in PLC   This output instruction is used to control physical properties such as temperature, pressure, liquid level, or flow rate of process loops. The PID instruction normally controls a closed loop using inputs from an analog input module and providing an output to an analog output module as a response to effectively hold a process variable at a desired set point. The PID equation controls the process by sending an output signal to the actuator. The greater the error between the setpoint and the process variable input, the greater the output signal, and vice versa. An additional value (feed forward or bias) can be added to the control output as an offset. The result of the PID calculation (control vari...

NE566 Function Generator Circuit Diagram

The NE566 Function Generator is a Voltage-Controlled Oscillator of exceptional linearity with buf fered square wave and triangle wave outputs. The frequency of oscillation is determined by an external resistor and capacitor and the voltage applied to the control terminal. The Oscillator CAN be programmed over a ten-to-one frequency range by proper selection of an external resistance and modulated over a ten-to-one range by the control voltage, with exceptional linearity.  FMAX = 1 MHz     WIDE 1000:1 Continuous Sweep Possible  NE566 Function Generator Circuit Diagram Pdf Datasheet  Sourced by : Circuitsstream

UML DIAGRAM

wact.jpg UML Class Diagram Example uml diagram tool UML Class Diagram Gliffy ... File:Uml diagram.svg ... UML class diagram example. UML 2.2 Diagrams Overview To auto layout the diagram ... UML Class diagram Class Diagram